Technical parameters of the low temperature air-cooled box type unit

MODEL

KD-3AD

KD-5AD

KD-8AD

KD-10AHD

KD-12AHD

KD-15AHD

KD-20AHD

KD-25AHD

Refrigeration capacity 

(KW)

-45℃

4

7

11

17

23

30

37

46

-55℃

2

5

7

10

13

18

21

27

-60℃

0.9

2

4.5

6

9

12

17

20

Rated power of the whole machine (KW)

6.4

10.6

14.35

17.35

21.45

27.95

35.45

43.8

Whole machine current (A)

13

22

29

35

43

56

71

88

Input power supply

380V/3PH/50Hz

Low temperature  level

Compressor

Type

Fully enclosed vortex type

Semi-closed piston type

Rated power (KW)

2.25

3.75

6

7.5

9

11.25

15

18.75

Refrigerant

R23

Evaporator

Type

Plate-type

Coolant

Ethyl alcohol

Flow rate of refrigerant (m³ / h)

1.3

2.4

3.7

5.8

8

10.3

12.7

15.8

Condenser

Type

Plate-type

High temperature  level

Compressor

Type

Fully enclosed vortex type

Semi-closed piston type

Rated power (KW)

3.75

6

7.5

9

11.25

15

18.75

22.5

Refrigerant

R22 / R404a / R407c

Evaporator

Type

Low temperature condenser

Condenser

Type

High-efficiency copper casing aluminum fin + low noise external rotor fan

Cooling air volume (m³ / h)

5000

8000

10000

15000

15000

20000

25000

30000

Safety precautions

Compressor overheating protection, high and low pressure protection, overtemperature protection, flow protection, phase sequence / phase deficiency protection, exhaust overheating protection, frost protection

Dimensions

Length (mm)

986

1261

1261

2001

2001

2604

2604

2523

Width (mm)

634

864

864

854

854

904

904

954

Height (mm)

1478

1921

1921

1608

1608

1915

1914

2024

Weight

Kg

300

510

650

1000

1250

1450

1500

1750

Nominal cooling capacity: ambient temperature 35℃, inlet and outlet temperature of carrying refrigerant -40℃ / -45℃ carrier refrigerant, glacier refrigerant

The Company reserves the power to change the technology without notice of any change